Description
Manufacturer: Wilo
Weight: 0.5 kg
SKU: 2210108
1x Module Required Per Pump Head (Twin Pumps require 2x Modules)
The flexible solution for building management system integration.
The Wilo-Connect module enables the optimal integration of the Wilo-Yonos MAXO into the building management system. Dual pump management is already integrated with no additional components required.
The Ext. OFF function ensures a soft start. The power needed to activate the pump is significantly reduced, decreasing the impact on the upstream switching elements. The pump operation is indicated by means of a collective run signal. The module can be used both in new installations and to upgrade existing systems.
Your advantages
- A universal module for the complete series that is suitable for single and twin-head pumps, for new installations and for retrofitting pumps that have already been installed
- Dual pump management already integrated without the need for additional components
- Plug connection allows easy installation
- Ext. OFF function ensures soft switching on and off for the preservation of upstream switching elements
- Monitoring of operational readiness via the building management system using collective run and fault signals
- Integrated dual pump management with fault indication for the pump affected and automatic switchover in case of a fault
The Wilo-Connect module Yonos MAXO is a retrofittable plug-in module for Wilo-Yonos MAXO/Yonos MAXO-D/Yonos MAXO-Z pumps.
The Wilo-Connect module Yonos MAXO is installed on the electronic module of the pump at the position of the Wilo plug.
Utilisation of the Wilo-Connect moduleYonos MAXO dispenses with external contactors and other switchgears as well as the associated installation workload. The load of customer-side switchgears (relays) due to high starting currents is reduced to a minimum by the Connect module Yonos MAXO.
Equipment/function
- Run signal display
- SSM collective fault signal as potential-free NC contact
- SBM collective run signal as potential-free NO contact
- Overriding Off control input (External Off)
- Integrated dual pump management with the functions:
- Main/standby operation with runtime-dependent (24 h) switchover from main to standby pump
- Fault-sensitive switchover to operational standby pump
Mains terminals
Terminal cross-section: max. 2.5 mm2
Signal terminals
Max. switching capacity: 250 V/1 A
Terminal cross-section: max. 1.5 mm2
Control terminal Ext. Off
Contact rating: 24 V DC, 10 mA
Terminal cross-section: min. 0.75 mm2, max. 1.5 mm2
Scope of delivery
Wilo-Connect module Yonos MAXO
2 fastening screws for cover installation
4 threaded cable glands M16
Installation and operating instructions